REX Joint Cord SG300 Fire Protection Cord

Product Information – Fire Protection Cords SG 300

Fire protection for joints tested according to DIN 4102 and European standard EN 1366-4 for use in both interior and exterior applications. The SG 300 fire protection cord is a flexible and elastic sealing cord made of mineral fibers braided with glass yarn. It is designed for fire-resistant sealing of horizontal and vertical construction joints in or between fire-resistant, room-enclosing walls and/or ceilings.

  • For interior and exterior applications
  • Fire resistance: F 30 A, F 60 A, F 90 A, F 120 A, F 180 A in walls and ceilings (DIN 4102)
  • EI 90 -H-X-F-W00 up to 55 (EN 13501)
  • Building material class A1 according to DIN 4102 and EN 13501-1

Applications

Fire protection cords are non-combustible joint fillers and fire protection seals according to DIN 4102–A1 and EN 13501-1. They are mainly used in expansion and movement joints in all areas of building construction, civil engineering, tunnel construction, and industrial construction. Depending on the configuration, they prevent the permissible temperatures from being exceeded and block the passage of fire and combustible gases for 30 to 180 minutes.

Processing

  • Applicable for stepped joints, linear butt joints, and shear joints
  • Shear movement in shear joints up to 10 cm
  • Lateral expansion up to 7.5% of joint width
  • Seals must be installed between two parallel joint flanks (tolerances allowed if maximum joint width is not exceeded)
  • Arrangement of the cord is generally free
  • In multilayer installation, joints must be staggered by 500 mm
  • For joints ≤ 30 mm: overlap of at least 100 mm required
  • For joints > 30 mm: butt joints permissible
  • Additional sealing with sealants or joint cover profiles allowed
  • Combustible filler material does not need to be removed
  • Bonding with Litaflex High Temperature Adhesive 800 permitted
  • Dimensioning and number of layers depend on fire resistance class and joint width (see tables)

Storage

Store in a cool and dry place.

Delivery Forms

  • 12 mm diameter × 100 m length
  • 15 mm diameter × 20 m length
  • 20 mm diameter × 20 m length
  • 30 mm diameter × 20 m length
  • 40 mm diameter × 20 m length
  • 50 mm diameter × 20 m length
  • 60 mm diameter × 10 m length

Permissible Configurations

Overview of fire-resistant configurations for installation in solid walls and ceilings ≥ 150 mm thick with a raw density ≥ 700 kg/m³:

Installation Case Joint Width (mm) Number of Layers / Arrangement Classification
(A) (B) 10 – 55 1, arbitrary EI 90-V-X-F-W 10–55 / EI 90-H-X-F-W 10–55
(A) (B) 55 1, arbitrary EI 120-V-X-F-W 55 / EI 120-H-X-F-W 55

Overview of fire-resistant configurations for installation in solid walls and ceilings ≥ 150 mm thick with a raw density ≥ 2,400 kg/m³ ± 20%:

Installation Case Joint Width (mm) Number of Layers / Arrangement Classification
(A) (C) 10 – 50 2, one layer each side, ≥ 25 mm from edge EI 90-H-M 65--F-W 10–50
(A) (B) 10 – 50 2 layers side by side, arrangement arbitrary EI 120-V-X-F-W 55 / EI 120-H-X-F-W 55
(A) (B) 10 – 27 / 37 – 55 4 layers side by side (10–27 mm) / 3 layers side by side (37–55 mm) EI 180-V-X-F-W 10–55 / EI 180-H-X-F-W 10–55